| Kit |
KIT-BZ25-XKE |
| Cooling capacity (Nominal) |
kW |
2,50 |
| Cooling capacity (Min) |
kW |
0,85 |
| Cooling capacity (Max) |
kW |
3,00 |
| EER (Nominal) (1) |
W/W |
3,68 |
| EER (Min) (1) |
W/W |
4,05 |
| EER (Max) (1) |
W/W |
3,33 |
| SEER (2) |
6,20 A++ |
| Pdesign (cooling) |
kW |
2,50 |
| Input power cooling (Nominal) |
kW |
0,68 |
| Input power cooling (Min) |
kW |
0,21 |
| Input power cooling (Max) |
kW |
0,90 |
| Annual energy consumption cooling (3) |
kWh/a |
141 |
| Heating capacity (Nominal) |
kW |
3,15 |
| Heating capacity (Min) |
kW |
0,80 |
| Heating capacity (Max) |
kW |
3,60 |
| Heating capacity at -7°C |
kW |
2,14 |
| COP (Nominal) (1) |
W/W |
4,06 |
| COP (Min) (1) |
W/W |
4,21 |
| COP (Max) (1) |
W/W |
3,46 |
| SCOP (2) |
4,20 A+ |
| Pdesign at -10°C |
kW |
1,90 |
| Input power heating (Nominal) |
kW |
0,78 |
| Input power heating (Min) |
kW |
0,19 |
| Input power heating (Max) |
kW |
1,04 |
| Annual energy consumption heating (3) |
kWh/a |
633 |
| Indoor unit |
CS-BZ25XKE |
| Indoor power source |
V |
230 |
| Indoor recommended fuse |
A |
16 |
| Indoor connection indoor / outdoor |
mm² |
4 x 1,5 |
| Indoor air flow (Cool) |
m³/min |
10,5 |
| Indoor air flow (Heat) |
m³/min |
11,1 |
| Moisture removal volume |
L/h |
1,5 |
| Indoor sound pressure (Cool -Hi) (4) |
dB(A) |
37 |
| Indoor sound pressure (Cool -Hi) (4) |
dB(A) |
37 |
| Indoor sound pressure (Cool -Lo) (4) |
dB(A) |
26 |
| Indoor sound pressure (Cool -Q-Lo) (4) |
dB(A) |
20 |
| Indoor sound pressure (Heat -Hi) (4) |
dB(A) |
37 |
| Indoor sound pressure (Heat -Lo) (4) |
dB(A) |
27 |
| Indoor sound pressure (Heat -Q-Lo) (4) |
dB(A) |
24 |
| Indoor dimension (Height) |
mm |
290 |
| Indoor dimension (Width) |
mm |
779 |
| Indoor dimension (Depth) |
mm |
209 |
| Indoor net weight |
kg |
8 |
| Outdoor unit |
CU-BZ25XKE |
| Outdoor air flow (Cool) |
m³/min |
30,4 |
| Outdoor air flow (Heat) |
m³/min |
30,4 |
| Outdoor sound pressure (Cool -Hi) (4) |
dB(A) |
48 |
| Outdoor sound pressure (Cool -Hi) (4) |
dB(A) |
48 |
| Outdoor sound pressure (Heat -Hi) (4) |
dB(A) |
49 |
| Outdoor dimension (Height) (5) |
mm |
542 |
| Outdoor dimension (Width) (5) |
mm |
780 |
| Outdoor dimension (Depth) (5) |
mm |
289 |
| Outdoor net weight |
kg |
24 |
| Pipe diameter (Liquid) |
Inch (mm) |
1/4 (6,35) |
| Pipe diameter (Gas) |
Inch (mm) |
3/8 (9,52) |
| Pipe length range |
m |
3 ~ 15 |
| Elevation difference (in/out) (6) |
m |
15 |
| Pipe length for additional gas |
m |
7,5 |
| Additional gas amount |
g/m |
10 |
| Refrigerant (R32) / CO2 Eq. |
kg / T |
0,54 / 0,36 |
| Operating range (Cool – Min) |
°C |
-10 |
| Operating range (Cool – Min) |
°C |
-10 |
| Operating range (Cool – Max) |
°C |
+43 |
| Operating range (Heat – Min) |
°C |
-15 |
| Operating range (Heat – Max) |
°C |
+24 |
Valoraciones
No hay valoraciones aún.